WEF6
Water cooler

WEF6 <br/>Water cooler
WEF6000A4

A From mechanical seal
B To mechanical seal
C Cooling water IN
D Cooling water OUT
E Vent
F Drain

WEF6
Water cooler

Features

Heat exchangers of the WEF6 range are used to cool process/barrier fluids in seal supply circuits. WEF6 heat exchangers are fully compliant with API 682 4th edition regulations. The process/barrier medium is directed through the tube, and the cooling medium is directed through the shell.
Venting and draining of the process/barrier medium side as well as the cooling water side is ensured. In addition, the heat exchangers can also be combined with a temperature instrument in the supply line to the mechanical seal (optional in accordance with API 682 4th edition).

Advantages

  • Operating limits up to 65 bar / 260 °C
    (943 PSI / 500 °F) (tube side):
    suitable for a wide range of operations
  • Cooling water and process side can be completely vented and drained
  • Seamless pipes on process side
  • Special design without welding inside the cooler
  • Higher cooling water velocity due to innovative cooler design
  • Stainless steel 316/316L: high resistance to corrosive media

Standards and approvals

  • PED 2014/68/EU (Design and production in accordance with EU Pressure Equipment Directive)
  • ASME VIII, Div. 1 possible (see notes)
  • API 682 4th edition

Notes

Design and production in accordance with EU Pressure Equipment Directive PED 2014/68/EU.
Design, calculation and production acc. to ASME VIII, Div. 1
(cooler not subject to ASME stamp requirements, piping <6")


Cleaning:
Process/barrier medium side and cooling water side: flush with a suitable solvent.

Recommended piping plans




Product variants

Designation WEF6100A4 WEF6101A4 WEF6000A4 WEF6001A4
Design code ASME VIII, Div. 1 PED 2014/68/EU ASME VIII, Div. 1 PED 2014/68/EU
Tube Shell Tube Shell Tube Shell Tube Shell
Process connections Flange 3/4",
600 lbs
NPT 3/4" Flange 3/4",
600 lbs
NPT 3/4" Flange 3/4",
600 lbs
Flange 3/4",
300 lbs
Flange 3/4",
600 lbs
Flange 3/4",
300 lbs
Drain / vent connection NPT 1/2" NPT 1/2" NPT 1/2" NPT 1/2"
Allowable pressure1) 65 bar
(943 PSI)
25 bar
(362 PSI)
65 bar
(943 PSI)
25 bar
(362 PSI)
65 bar
(943 PSI)
25 bar
(362 PSI)
65 bar
(943 PSI)
25 bar
(362 PSI)
Allowable temperature
cooling water side (shell side)1)
-29 °C … +150 °C
(-20 °F … +302 °F)
-29 °C … +150 °C
(-20 °F … +302 °F)
-29 °C … +150 °C
(-20 °F … +302 °F)
-29 °C … +150 °C
(-20 °F … +302 °F)
Allowable temperature
process/barrier medium side (tube side)1)
-29 °C … +260 °C
(-20 °F … +500 °F)
-29 °C … +260 °C
(-20 °F … +500 °F)
-29 °C … +260 °C
(-20 °F … +500 °F)
-29 °C … +260 °C
(-20 °F … +500 °F)
Cooling capacity (kW)2) 10 10 10 10
Cooling capacity (kW)3) 3 3 3 3
Required cooling water quantity (m³/h) 0.6 0.6 0.6 0.6
Metal parts 316/316L 316/316L 316/316L 316/316L


Other versions on request.

1) Standard design data, extendend pressure / temperature rating on request.
2) Guidelines with barrier/buffer fluid water 60 °C – cooling water 20 °C.
3) Guidelines with barrier/buffer fluid oil 60 °C – cooling water 20 °C.

Similar products

WDK

WDK5120 heat exchangers are used to cool process/barrier fluids in seal supply circuits. The heat exchanger has a wound double helix around the guide tube. Process/barrier medium in the tubes, cooling medium around the tubes.

Circulation based on API 682 / ISO 21049: Plan 21, Plan 22, Plan 23, Plan 41

WE6

Heat exchangers of the WE6 range are used to cool process/barrier fluids in seal supply circuits. WE heat exchangers are available in two standard sizes and are API 682 conform. The process/barrier medium is directed through the tube and the cooling medium through the shell.

For simple draining or venting of the cooling water side, the heat exchanger can also be supplied with ventilation/drainage ball valves. In addition, the heat exchangers can also be combined with a temperature instrument in the supply line to the mechanical seal (optional in accordance with API 682).

Circulation in accordance with API 682 / ISO 21049: Plan 21, Plan 22, Plan 23, Plan 41

WED

Heat exchangers of the WED range are used to cool process/barrier fluids in seal supply circuits. Designed as a tubular heat exchanger with integrated guide plates, the process/barrier medium is directed through the shell of the WED and the cooling medium through the tubes.

Circulation based on API 682 / ISO 21 049: Plan 21, Plan 22, Plan 23, Plan 41
Contact

Inquire about individual solutions

We develop and produce customer-specific special and individual solutions for every application.

Inquire now Discover reference projects